Dronten 2022: The 150 kV Fault That Protection Failed to Clear

Learning
SubstationsOverhead LinesProtectionIncidentsSolar
Published: 16 Nov 2026

Keywords: protection, electrical, zendure, 2022, fault, incident, failure, below, solarflow, 150

Director's commentary

Summary

Add your own SEO-focused summary here.

Key points

  • Point 1
  • Point 2

Related videos

  • [Example related video](/videos/example)

Description

Check out Zendure's Black Friday Deal below and get an extra 8% off with code 7OS7Q, valid until Jan 4th 2027!

☀️ SolarFlow 2400 Pro** — £1,399 → £1,099 (Save £300!)

👉 Shop Zendure: https://bit.ly/4iPGu6C
---

On 2 September 2022, a 150 kV transmission line in the Netherlands suffered an extraordinary electrical fault. What should have been cleared in a fraction of a second continued for 4 minutes and 22 seconds.

Thousands of amps flowed through the fault, an electrical arc burned at the substation, and overhead conductors became so hot that they began smoking and sagging towards the railway infrastructure below.

But why didn't the protection stop it?

In this episode of Fault Recorder, we investigate the Dronten 2022 grid incident, uncovering how a series of commissioning, switching and protection failures combined to turn a routine operation into a major electrical incident.

We'll explore the circuit breaker that wouldn't open normally, the earthing switch operated onto a live 150 kV circuit, the local control selector that prevented a protection trip, and the breaker-failure protection that failed to provide its intended backup.

We'll also look at the lessons this incident offers for electrical safety, commissioning, protection engineering and the importance of independent layers of defence.

Because sometimes the most serious incidents aren't caused by one spectacular failure, but by several smaller ones happening at exactly the wrong time.

📚 **Sources and further reading**

DNV – Investigation into the Flevoland power failure (2022):
https://tennet-drupal.s3.eu-central-1.amazonaws.com/default/2023-02/23-2534%20DNV%20Publieke%20samenvatting%20onderzoeksrapport%20Flevoland%202%20september%202022_0.pdf

PAC World – Combination of Factors Caused Disturbance Flevoland:
https://www.pacw.org/combination-of-factors-caused-disturbance-flevoland-nl

⚡ Subscribe to The Electric Brit for more investigations into electrical engineering, power systems, grid failures and the technology keeping our lights on.

Corrections:
12:54 This is the case in their report. In the UK the local remote switch should NOT block protection trip commands. Only putting protection in test mode or pulling fuses and links will do this.

#Zendure #SolarFlow #SolarFlow2400Pro #BlackFriday #FaultRecorder #ElectricalEngineering #PowerGrid #Dronten #TheElectricBrit